1.1 Specifications
Control Panel Specifications
PC1575 (standard option): one low current PGM output
and one low current PGM output/input.
PC1575 (2-wire smoke option): one low current PGM
output and one high current PGM output/input.
Flexible Zone Configuration:
Six fully programmable zones
Seven Access Codes: five User, one Master and a
second Master code
Normally Closed, Single EOL, Double EOL
2-wire Smoke Zone or Auxiliary Zone
21 Zone Types, 6 Programmable Zone Options
Audible Alarm Output:
Supervised Bell Output (current limited at 3 amps), 12V
DC
Steady or Pulsed Output
EEPROM Memory:
Does not lose programming or system status on
complete AC and Battery failure
Programmable Outputs:
One programmable voltage output and one
programmable voltage output/input; 30 programmable
options
PC1575 (standard option):
PGM1 = one low current (50mA) PGM output
PGM2 = one low current (50mA) PGM output/input.
PC1575 (2-wire smoke option):
PGM1 = one low current (50mA) PGM output
PGM2 = one high current (300mA) PGM output/input
with 2-wire smoke detector capability
Please read Appendix D “PGM Output Options”
carefully for important information.
Powerful 1 Amp Regulated Power Supply:
550 mA Auxiliary Supply, 12 V
DC
Positive Temperature Coefficient (PTC) components
replace fuses
Supervision for loss of AC Power, Low Battery
Internal Clock Locked to AC Power Frequency
Power Requirements:
Transformer = 16.5 V
AC, 40VA
Battery = 12 volt 4 Ah minimum rechargeable sealed
lead acid
Remote Keypad Specifications:
Three Different Keypads Available:
- PC5506 six zone LED keypad
- LCD5500 Alphanumeric keypad
- PC1575RK six zone LED keypad
- SL-75 six zone LED keypad
The PC5506 and LCD5500 keypads have 5 Fully
Programmable Function Keys
Connect up to 8 Keypads
Four Wire (Quad) Connection to KEYBUS
Built in Piezoelectric Buzzer
SECTION1
Digital Communicator Specifications:
Supports Major Formats including SIA and Contact ID
Event Initiated Personal Paging
Three Programmable Phone Numbers
Two Account numbers
Supports LINKS 1000 Cellular Communication
DTMF and Pulse Dialing
DPDT Line Seizure
Anti-jam Feature
Split Reporting of Selected Transmissions to Each
Telephone Number
System Supervision Features:
The PC1575 continuously monitors a number of possible
trouble conditions including:
AC Power Failure
Trouble by Zone
Tamper by Zone
Fire Trouble
Telephone Line Trouble
Failure to Communicate
Low Battery Condition
Bell Output Trouble
Module Fault (Supervisory or Loss of Internal Clock
AUX Power Supply Fault Tamper)
False Alarm Prevention Features:
Audible Exit Delay
Audible Exit Fault
Communication Delay
Urgency on Entry Delay
Quick Exit
Additional Features:
Auto Arm at Specified Time
Keypad Activated Alarm Output and Communicator
Test
All modules connect to the system via a four wire
KEYBUS up to 1000’/300m from main panel
Event Buffer can be printed using PC5400 RS232 Serial
Interface module
Supports the ESCORT 5580 Voice Prompt Module with
Automation/Lighting Control
An Event Buffer which records the past 100 events with
both the time and date at which they occurred
Uploading and Downloading capability
• Local Downloading capability through the use of the
PC-LINK Adaptor
UL Installation
This equipment is UL Listed in accordance with UL1023
(Household Burglar Alarm System Units), UL985 (Household
Fire Warning System Units), UL1635 (Digital Alarm Annunciator
System Units), UL365 (Police Station Connected Burglar
Alarm Units and Systems), UL609 (Local Burglar Alarm Units
and Systems), UL1610 (Central Station Burglar Alarm Units).
This equipment has the capability of being programmed for
operational features that are not allowed for UL Listed Systems
or being connected to accessories not permitted.
Refer toRefer to
Refer toRefer to
Refer to
Appendix E for summary of requirements.Appendix E for summary of requirements.
Appendix E for summary of requirements.Appendix E for summary of requirements.
Appendix E for summary of requirements.
PC1575 System Introduction
Zobrazit stránku 0
1 2 3 4 5 6 ... 42 43

Shrnutí obsahu

Strany 1 - PC1575 System Introduction

11.1 SpecificationsControl Panel SpecificationsPC1575 (standard option): one low current PGM outputand one low current PGM output/input.PC1575 (2-wire

Strany 2 - 1.3 Out of the Box

KEYPADVCOMMANDS10• [2] – Auto-Arm Enable/DisableAuto-Arming will not work unless it is enabled for thesystem. To enable or disable auto-arming, press

Strany 3 - Getting Started

KEYPADVCOMMANDS113.5 Function KeysThe function keys only appear on the PC5506 andLCD5500 keypadsThere are five function keys on the PC5506 and LCD5500

Strany 4 - 2.5 Keypad Assignment

12SECTION4The following section of the manual describes the Installer’sProgramming function and how to program the various sections.You must read the

Strany 5 - 2.8 Zone Wiring

13HOWVTOVPROGRAMRefer to Section 5 in this manual to determine what eachoption represents and whether the light should be ON orOFF for your applicatio

Strany 6 - G E T T I N G S T A R T E D

14The following section explains the operation of all programmablefeatures and options and provides a summary of all correspondingprogramming location

Strany 7 - Keypad Commands

15P R O G R A M D E S C R I P T I O N S[10] 24 Hour Supervisory Buzzer ZoneIf this zone is violated when the system is either armed ordisarmed, the p

Strany 8 - [2] Trouble Display

16P R O G R A M D E S C R I P T I O N SPhone numbers can be up to 32 digits which will allow youto add special digits if required. To program the pho

Strany 9

17P R O G R A M D E S C R I P T I O N Sthe Fire Keys on any keypad are pressed for two seconds.The panel will transmit a Keypad Auxiliary Alarm Repor

Strany 10 - KEYPADVCOMMANDS

18P R O G R A M D E S C R I P T I O N S• 3/1, 3/2, 4/1 or 4/2 • 1400 or 2300 Hz handshake• 20 bits per second • non-extendedAdditional Notes on Pulse

Strany 11 - 3.5 Function Keys

19P R O G R A M D E S C R I P T I O N SWhen power is applied to the panel, downloadingwill be enabled for six hours. This will allow you toperform do

Strany 12 - How to Program

SYSTEMVINTRODUCTION21.2 Additional Devices1.2.1 KeypadsA maximum of eight keypads can be connected to thecontrol panel and can be any combination of t

Strany 13 - 4.5 Viewing Programming

20P R O G R A M D E S C R I P T I O N SPeriodic Test Transmission Reporting Code.. Section [46]Test Transmission Time of Day ...

Strany 14 - Program Descriptions

21P R O G R A M D E S C R I P T I O N SBy default, the Swinger Shutdown limit is set to [003]. Thepanel will not send more than three alarm signals f

Strany 15 - 5.4 Communicator – Dialing

22P R O G R A M D E S C R I P T I O N SLINKS is Backup of Land Lines option must be selected.When used as a backup communicator, the panel will attem

Strany 16

23NOTE: For UL listed systems, refer to the UL Requirements section in Appendix E.For the RecordCustomer:_____________________________________________

Strany 17

24P R O G R A M M I N G W O R K S H E E T S[00] Keypad Assignment (Section 2.6 “Keypad Assignment”)(Section 2.6 “Keypad Assignment”)(Section 2.6 “Key

Strany 18 - 5.9 Downloading

P R O G R A M M I N G W O R K S H E E T S25[03] Installer’s Code (Section 4 “How to Program”)Default1575 I_______I_______I_______I_______I[04] Master

Strany 19 - 5.11 Siren Supervision

26P R O G R A M M I N G W O R K S H E E T S[10] Third System Option CodeDefault Option ON OFF SectionOFFI________I 1 Arm / Disarm Bell Squawk Enabled

Strany 20 - 5.16 Swinger Shutdown

P R O G R A M M I N G W O R K S H E E T S27Note: For sections [31] to [46], the contents of every section by default is [F].[31] First Telephone Num

Strany 21

28P R O G R A M M I N G W O R K S H E E T S[42] Opening (Disarming) Reporting Codes, Access Codes 1-6 (Section 5.7 “Communicator – Repor(Section 5.7

Strany 22 - 5.27 Installer’s Lockout

P R O G R A M M I N G W O R K S H E E T S29[53] Openings & Closings Communicator Call Directions (Section 5.4 “Communicator – Dialing”)(Section 5

Strany 23 - Programming Worksheets

3SECTION2The following Sections provide a thorough description of how towire and configure devices and zones.2.1 Installation StepsThe following steps

Strany 24 - Basic System Programming

30P R O G R A M M I N G W O R K S H E E T S[67] LINKS 1000 Preamble (First Telephone Number) (Section 5.23 “LINKS 1000 Cellular Communicator”)(Se

Strany 25

P R O G R A M M I N G W O R K S H E E T S31[87]PC5400 Programming (Printer Module) (Section 5.24 “On-Site Printer”)(Section 5.24 “On-Site Printer”)(S

Strany 26 - Advanced System Programming

32The Partition ID Codes must be 4 digits. All reporting codes must be 2 digits.The following is a list of Contact ID reporting codes. The first digit

Strany 27 - Communicator Programming

33SIA FormatLevel 2 (Hardcoded)The SIA communication format used in this product follows the level 2 specifications of the SIA DigitalCommunication St

Strany 28

34Programming LCD KeypadsA P P E N D I X CIf you have an LCD5500 Keypad, additional programming is required for proper operation. The following is a

Strany 29 - 5.105.10

35[62] Third User Display MaskDefault Option ON OFFON I_______I 1 System Test prompt ON System Test prompt OFFONI_______I 2 Time and Date prompt ON Ti

Strany 30 - Downloading Programming

Establishing PGM Output TypesEach PGM output is designed so that when activated by thepanel, the terminal will switch to ground.PGM 1 – 50mA CurrentPG

Strany 31 - Special Installer Functions

[11] TLM and AlarmThe PGM output switches to ground when the systemexperiences both a telephone line trouble and an alarm.When the system is armed, th

Strany 32 - Contact ID

The following requirements apply to UL Listed systems:1. All components of the system should be UL listed for the intendedapplication.2. If this syste

Strany 33 - SIA Format

Control Panel Wiring Diagram

Strany 34 - Programming LCD Keypads

G E T T I N G S T A R T E D4Programmable Output Terminals – PGM1 and PGM2Please refer to Appendix D “PGM Output Options”Appendix D “PGM Output Option

Strany 35

Table of ContentsTABLE OF CONTENTSNOTICE!You must read this entire manual, including all notices and warnings, in order to install thissystem so that

Strany 36 - PGM Output Options

TABLE OF CONTENTSTABLEVOFVCONTENTSLimited WarrantyDigital Security Controls Ltd. warrants that for a period of twelve months from the date of purchase

Strany 37

Industry Canada NoticeAVIS: L’étiquette de l’Industrie Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme

Strany 38 - Appendix E

© 1997 Digital Security Controls Ltd.1645 Flint Road, Downsview, Ontario, Canada M3J 2J6Tel. (416) 665-8460 • Fax (416) 665-7498 • Tech. Line 1-800-38

Strany 39 - Control Panel Wiring Diagram

G E T T I N G S T A R T E D52.6 SupervisionBy default, all modules are supervised upon installation.Supervision is enabled at all times so that the p

Strany 40 - Table of Contents

G E T T I N G S T A R T E D6All fire zones must be wired according to the followingdiagram:2.8.5 Fire Zone Wiring – 2-Wire Smoke DetectorsThis option

Strany 41 - Limited Warranty

7SECTION3The PC1575 alarm panel can be accessed, controlled andcompletely programmed via any keypad on the system. The LEDkeypad uses function and zon

Strany 42 - IMPORTANT INFORMATION

KEYPADVCOMMANDS8zone—due to a bad contact or damaged wiring—untilservice can be provided.If the Code Required for Bypass option is enabled, onlyuser c

Strany 43

KEYPADVCOMMANDS9reporting code(s) programmed in section [45] will betransmitted along with the unreported events from anearlier unsuccessful communica

Komentáře k této Příručce

Žádné komentáře